STATEMENT OF SPECIAL

INSPECTIONS AND TESTS

As required by the Building Code of NYS (BCNYS)                             

BCNYS § 1704.1.1 requires the project Design Professional to complete the Statement of Special Inspections and Tests.  Completion of the Statement of Special Inspections & Tests and submission to the Office of Facilities Planning with the Construction Permit Application is a condition for issuance of the Building Permit.

School District

 

Building

Project Title

 

SED Project #

 

Project Address

Architect/Engineer

 

Name of Person Completing this Statement

 

               Phone

               Date

Comments

 

         

 

 

 

 

INSPECTION AND TESTING (Continuous & Periodic is as Defined by the BCNYS)

 

CONTINUOUS

PERIODIC

REFERENCE

STANDARD

BCNYS

REFERENCE

CHECK IF

REQUIRED

 

 

IDENTIFY SPEC SECTION AND PROVIDE CLARIFYING NOTES IF NECESSARY

A. Steel Construction

 

 

 

 

 

 

1.      Material verification of high-strength bolts, nuts and washers.

 

X

Applicable ASTM material specifications.  AISC ASD, Section A3.4; AISC LRFD, Section A3.3

1704.3



 

2.      Inspection of high-strength bolting.

X

X

AISC LRFD, Section M2.5

1704.3,

1704.3.3



 

3.      Material verification of structural steel.

 

 

ASTM A 6 or A 568

1704.3,

1708.4



 

4.      Material verification of weld filler materials.

 

 

AISC, ASD, Section A3.6; AISC LRFD, Section A3.5

1704.3



 

5.      Inspection of welding:

 

 

AWS D1.1, D1.3, D1.4; ACI 318: 3.5.2

1704.3,

1704.3.1,

1903.5.2



 

               a.  Structural steel

X

X

 

 



 

               b.  Reinforcing steel

X

X

 

 



 

6.      Inspection of steel frame joint details.

 

X

 

1704.3,

1704.3.2



 

B.  Concrete Construction

 

 

 

 

 

 

1.      Inspection of reinforcing steel, including prestressing tendons, and placement.

 

X

ACI 318: 3.5, 7.1-7.7

1704.4,

1903.5,

1907.1,

1907.7,

1914.4



 

2.      Inspection of reinforcing steel welding.

 

 

AWS D1.4; ACI 318: 3.5.2

1704.4,

1903.5.2



 

3.      Inspection of bolts to be installed in concrete prior to and during placement.

X

 

 

1704.4,

1912.5



 

4.      Verify use of required design mix.

 

X

ACI 318: Ch. 4, 5.2-5.4

1704.4,

1904,

1905.2-1905.4,

1914.2,

1914.3



 



 

5.      Sampling fresh concrete: slump, air content, temperature, strength test specimens.

X

 

ASTM C 172, C 31; ACI 318: 5.6, 5.8

1704.4,

1905.6,

1914.10



 

6.      Inspection of placement for proper application techniques.

X

 

ACI, 318: 5.9, 5.10

1704.4,

1905.9,

1905.10,

1914.6,

1914.7,

1914.8



 

7.      Inspection for maintenance of specified curing temperature and techniques.

 

X

ACI, 318: 5.11, 5.13

1704.4,

1905.11,

1905.13,

1914.9



 

8.      Inspection of prestressed concrete.

X

 

ACI 318: 18.18, 18.164

1704.4



 

9.      Erection of precast concrete members.

 

X

ACI 318: Ch. 16

1704.4



 

10.   Verification of in-situ concrete strength prior to stressing of tendons and prior to removal of shores and forms from beams and slabs.

 

X

SVI 318: 6.2

1704.4,

1906.2



 

C.     Masonry Construction

L1 = Level 1 Inspection required for nonessential facilities.

L2 = Level 2 Inspection required for essential facilities.  In general, schools are not considered essential facilities unless they are a designated emergency shelter.

 

 

ACI 530/ ASCE 5/TMS 402, Ch. 35

ACI 530.1/ ASCE 6/TMS 602, Ch. 35

 

 

 

1.      Verify to ensure compliance:

 

 

 

 

 

 

a.  Proportions of site prepared mortar                                            and grout.

 

X

L1

L2

 

2.6A

1704.5



 

b.  Placement of masonry units and construction of mortar joints.

 

X

L1

L2

 

3.3B

1704.5



 

c.  Location and placement of reinforcement, connectors, tendons, anchorages.

 

X

L1

L2

 

3.4,

3.6A

1704.5



 

d.  Prestressing technique and installation.

 

X

L1

L2

 

3.6A,

3.6B

1704.5



 

e.  Grade and size of tendons and anchorages.

 

X

L1

L2

 

2.4B,

2.4H

1704.5



 

f.  Grout specs prior to grouting.

X

L2

 

 

3.2D

1704.5



 

g.  Placement of grout.

X

L2

 

 

3.5

1704.5



 

h.  Grouting of tendons.

X

L2

 

 

3.6C

1704.5



 

2.      Inspection shall verify:

 

 

 

1704.5



 

a.  Size and location of structural elements.

 

X

L1

L2

 

3.3G

1704.5



 

b.  Type, size, and location of anchors.

X

L2

X

L1

1.15.4, 2.1.1

 

1704.5



 

c.  Specified size, grade, and type of reinforcement.

 

X

L1

L2

1012

2.4, 3.4

1704.5



 

d.  Welding of reinforcing bars.

X

L1

L2

 

2.1.8.6,

2.1.8.6

 

1704.5,

2108.9.2.11



 

e.  Cold/hot weather protection of masonry construction.

 

X

L1

L2

 

108

1704.5,

2104.3,

2104.4



 

f.  Prestressing force measurement and application.

X

L2

X

L1

 

3.6B

1704.5



 

3.      Inspection prior to grouting.

 

X

L1

L2

1.12

3.2D,

3.4,

2.6B,

3.3B

1704.5



 

4.      Grout placement.

X

L1

L2

 

 

3.5,

3.6C

1704.5



 

5.      Preparation of grout specimens, mortar specimens, and/or prisms.

X

L1

L2